ONLINE UPS

In order to keep a battery charged, an online UPS (Uninterrupted Power feed) converts incoming AC power into DC power and then back into AC power to feed the load. This form of UPS continually supplies power to the connected load from its battery backup. ​

For industries, telecommunication, and medical equipment, even a few milliseconds of transfer time might result in major interruptions.

SPECIFICATIONS
Particular
Description
Input Voltage
230VAC +- 20%
Output Voltage
230Volts ± 1%
Phase Single
Power Factor
0.8 to unity
Input Freq 45 Hz to 55 Hz
DC Volt 36VDC – 192VDC or as per customers specification
Output Freq 50 Hz +- 0.1%
Isolation Xmer Provided
Topology: IGBT BASED
Web form Sine wave
Crest Factor 3:1
THD <3% on Liner Load
Inv Efficiency > 90%
Over all Effi >80%
Overload: 110% for 30 Min 125% for 10 minutes 150% for 1 minutes
Transient Response For 0 to 50% & 50% to 100% load Change voltage remains within ± 5%
Protection Input and Output Over Voltage / Under Voltage DC Over Voltage / Under Voltage
Alarm Mains Fail, Battery Low , Inverter Trip
Display LED / LCD Display Output – Voltage / Current / Freq. Input – Voltage / Current / Freq
Indication Mains – On / High / Low / Fail DC – On / High / Low Inverter – On / High / Low / Overload
Switchgear MCB Input / Output
Temp. 0 to 40 C
Protection IP- 20, 21
Humidity Upto 95% Rh (non-condensing)
Cooling: Upto 95% Rh (non-condensing)
Auto Bypass: Available
Noise 1 mtr <55 dB